Posts

CaTV | Subscriber outlet to subscriber terminal

Image
  Abbreviation Dimension Tolerance L [Length] 68.8 mm(2.71 in.) 1.02 mm (0.040 in.) H [Height] 35.1 mm (1.38 in.) 0.90 mm (0.035 in.) T [Depth] 1.40 mm (0.055 in.) 0.64 mm (0.0.25 in.) R [Corner Radius] 4.06 mm (0.160 in.) max -- C [Distance to first obstruction] 30.5 mm (1.2 in.) min --   Design Consideration for specification from subscriber outlet to subscriber terminal. At least one TV box shall be planned for each room with the following construction and dimension. Wall plates shall have a 75 ohms barrel splice "F" female both ends 3/8" - 32 threads per inch mounted in the center. A washer and nut, matched specifically in the female splice adapter, shall secure the barrel splice to the wall plate. When attaching the cable to the splice adapter, special care shall be taken to avoid over tightening.  EXCERPTS | Cable Television System B

FDAS | Emergency Communication Systems

Image
  Emergency Communication Systems (ECS) are designed to alert and evacuate occupants of a building in case of emergency situations. This is a segment of an Fire Detection and Alarm System that broadcasts the existence of a fire or an emergency situation, or sends information necessary to facilitate an appropriate action. ECS Basic Types Emergency Voice Alarm Communication (EVAC) This is a segment of an Fire Detection and Alarm System that broadcasts information during an emergency to the occupants of a building or facility and instructs appropriate actions to them, such as evacuating. it is conveyed by audible or visible means, or both. Two-way Emergency Communications System This is a segment intended for use by the building fire safety personnel or by the fire fighters and first responders to both exchange information and to communicate information, such as condition of local environment, condition of persons, to give assurance that help is on the way, or any other instructions. Emer

Why we use the end of line resistor in fire alarm system?

Image
  Kidde EOL-15 End of Line Resistor 15K Ohm The function of an end of line (EOL) resistor is to monitor the integrity of the circuit in a fire alarm system. This is achieved by placing the resistor at the end of the wiring loop, completing the electrical circuit. The control panel of the fire alarm system continuously monitors the resistance of the circuit, which should match the resistance value of the EOL resistor. Any changes from readings may indicate a potential issue, prompting the system to signal a trouble condition. An EOL resistor should always be installed as the last device in the loop and never inside the control panel. Placing resistors anywhere other than the end of the line does not serve a purpose. Open Circuit Detection When there is a break in the wiring or a device is disconnected, it creates an open circuit. This means that the electrical current cannot complete its path through the circuit, resulting in an increase in resistance. The EOL resistor, placed

FDAS | Notification Appliances

Image
    The alarm sound from audible notification appliances shall b e clearly audible throughout the floor and / or  building in which they are installed. It should be sufficient to warn and initiate evacuation of all occupants for whom the alarm sound is intended. A sufficient number of audible notifications appliances shall be used to produce a minimum sound level of 65 dBA, or 10 dB above the ambient noise level having a duration of at least 30 seconds, whichever is greater, measured 1.4 meters above the floor in the area required to be served by the system. The sound level produced by audible notification appliances and the ambient noise combined shall not exceed 115 dBA. If the sound level required is higher than 115 dBA, visual notification appliances such as strobes shall be used in addition to the audible notification appliances generating the maximum allowable sound level. In bars, nightclubs, and other entertainment places where the ambient noise level is high, the sound system

FDAS | Deciding between a Single Panel and a Network Panel

Image
  Each building shall have at least one fire alarm control panel (FACP). However, two or more panels networked together shall be required in the following setting below. ♦ If the number of buildings in a multi-building complex exceeds three, or; ♦ If the total floor area of all the buildings in a multi-building  complex exceeds 40,000 square meters. For each panel in the network shall protect approximately the same floor area.   In a network of panels, there shall be at least one network display that shows the alarms and troubles of all panels in the network. The network display shall also be able to acknowledge, silence, and reset all alarms and trouble alerts. Location and Environments The fire alarm control panel or network display shall be located in the fire command center of the building or complex. In the absence of a fire command center, it should be located ideally in a position clearly visible from the main entrance of a lobby. However, if it is located in another location ac

FDAS | Design Requirements

Image
    The general purpose of a Fire Detection and Alarm System is to detect at the earliest  stage of a fire, and to give a announce via an alarm to alert the occupants so that appropriate action can be decided. The alert display within the FDAS shall also be notified  so that an appropriate action and maintenance can be initiated to keep the system in normal operating condition at all times. All the individual components of an Fire Detection and Alarm System shall be compatible with each other. Suggest to have one brand for a system. All system equipment shall be approved and listed by institutions  recognized by the relevant authority, and suitable for use in the Philippines, considering ambient conditions such as temperature and relative humidity, and electricity supply of 220 Vac at 60 Hz. If any equipment is located in an area where it is exposed to corrosion, high humidity, extreme temperature or other special condition, the design and installation shall be such that the reliabilit

FDAS | Central Station Alarm Monitoring for Commercial Establishments

Image
  Photo Credits | Macrovector   If necessary all installed Fire Detection and Alarm System should subscribe to the alarm monitoring services of a central station. All alarm signals received by the monitoring central station shall be forwarded or redirected to the nearby fire fighting authorities. The competence of the operators of the central station shall be certified by the manufacturer of the receiving system of equipment, or by an organization acceptable to the authority having jurisdiction (AHJ). Central station monitoring services are the best way to maintain peace of mind and keep your establishment secured 24 hours a day, 7 days a week. Central station alarm monitoring connects your alarm systems to an Underwriters Laboratory (U.L.) listed Central Station which is expected to respond any time an alarm is triggered. The central station will then notify the appropriate authorities of the incident so that help comes quickly. This can be very important if no one is on the premises